Dantherm TKS 60 – high capacity free cooling unit

High capacity free cooling unit

TKS 60 is high-capacity free air cooling designed to control the internal environment of communication shelters using a minimum of energy.

By means of ventilation in an overpressure system, the TKS 60 efficiently removes excess heat from the temperature-sensitive equipment – maintaining the internal temperature within defined limits.

Dantherm TKS 60 – high capacity free cooling unit
Dantherm TKS 60 – high capacity free cooling unit

Key features

  • Total heat management – designed for energy-efficiency with maximum use of controlled ventilation
  • Energy-efficient cooling strategy – automatic change between cooling modes
  • Protect your equipment – standard M5 fine bag filter and optional AirMaze (pat.pend.)
  • Avoid unsceduled service visits – plan service with built-in filter monitor
  • Wide geographical usage – ambient temperature operating range from -25 to 55°C
  • User friendly display for climate control and ethernet and SNMP for remote control
  • Integrated CC3000 control system

Product specifications

SpecificationsUnitsTKS 60 230V AC
Nominal air flow
m3/h
4,200
Nominal cooling capacity in W/K (Δt = 1°C)
W/K
1,400
Nominal fan power consumption (at 100% fan speed)
W
782
Filter class
ePM10 55 % (F5)
Fan nominal voltage
V
230V AC
Sounds pressure @ 1m
dB(A)
67
Controller
Type
CC3000
Communication interface
Type
Ethernet SNMP, Modbus
Product size (h x w x d)
mm
1100 x 600 x 600
Net weight
kg
53
SpecificationsUnitsTKS 60 48V DC
Nominal air flow
m3/h
3,200
Nominal cooling capacity in W/K (Δt = 1°C)
W/K
1,050
Nominal fan power consumption (at 100% fan speed)
W
374
Filter class
ePM10 55 % (F5)
Fan nominal voltage
V
48 DC (42-57V DC)
Sounds pressure @ 1m
dB(A)
64
Controller
Type
CC3000
Communication interface
Type
Ethernet SNMP, Modbus
Product size (h x w x d)
mm
1100 x 600 x 600
Net weight
kg
51

Suitable for

  • Data centres and telecoms