Dantherm Group
Dantherm

Dantherm DFC 350-450 – displacement free cooling unit

Ventilation units

The Dantherm DFC 350 and 450 are slim passive cooling units utilising the displacement free air cooling technology. The units are designed to remove excess heat from small rooms with electronic equipment, where the air is stagnant.

Dantherm DFC 350-450 – displacement free cooling unit
Dantherm DFC 350-450 – displacement free cooling unit
Combined free cooling
Combined free cooling

Key features

  • Stay in control – total heat management with control of several external units
  • Ensure energy-efficient cooling strategy – automatic change between cooling modes
  • Protect your equipment – F5 displacement bag filter keeps your rooms clean
  • Avoid unscheduled service visits – plan service with built-in filter monitor
  • Wide geographical usage – ambient temperature operating range from -25 to 55°C
  • Silent and energy-efficient – very low air flow and fan speed
  • Integrated CC3000 control system

Product specifications

SpecificationsUnitsDFC 350 48V DC
Operating temperature range
°C
-25 to +55
Maximum cooling capacity at 25°C ambient, Δt = 10°C
W
3,000
Air flow – maximum
m3/h
514
Input voltage range
VDC
48VDC (42-57VDC)
Power consumption 50/80/100%
W
11/23/40
Sound level, 100% @ 3m
dB(A)
43
Controller
Type
CC3000
Communication interface
Type
Ethernet SNMP, Modbus
Product size indoor (h x w x d)
mm
1982 x 385 x 166
Net weight
kg
10
SpecificationsUnitsDFC 350 230V AC
Operating temperature range
°C
-25 to +55
Maximum cooling capacity at 25°C ambient, Δt = 10°C
W
3,000
Air flow – maximum
m3/h
514
Input voltage range
VDC
230V AC (200 to 277)
Power consumption 50/80/100%
W
8/20/35
Sound level, 100% @ 3m
dB(A)
44
Controller
Type
CC3000
Communication interface
Type
Ethernet SNMP, Modbus
Product size indoor (h x w x d)
mm
1982 x 385 x 166
Net weight
kg
10
SpecificationsUnitsDFC 450 48V DC
Operating temperature range
°C
-25 to +55
Maximum cooling capacity at 25°C ambient, Δt = 10°C
W
5,000
Air flow – maximum
m3/h
1,100
Input voltage range
VDC
48VDC (42-57VDC)
Power consumption 50/80/100%
W
12/25/40
Sound level, 100% @ 3m
dB(A)
43
Controller
Type
CC3000
Communication interface
Type
Product size indoor (h x w x d)
mm
2054 x 487 x 235
Net weight
kg
13
SpecificationsUnitsDFC 450 230V AC
Operating temperature range
°C
-25 to +55
Maximum cooling capacity at 25°C ambient, Δt = 10°C
W
5,000
Air flow – maximum
m3/h
1,100
Input voltage range
VDC
230V AC (200 to 277)
Power consumption 50/80/100%
W
16/41/61
Sound level, 100% @ 3m
dB(A)
44
Controller
Type
CC3000
Communication interface
Type
Product size indoor (h x w x d)
mm
2054 x 487 x 235
Net weight
kg
13

Suitable for

  • Data centres and telecoms