Dantherm Group
Dantherm

Dantherm AC-M6 – tent cooler

Tent cooler

The high performing AC-M6 air-conditioning solution allows humanitarian organisations to procure and use the equipment for refugee camps, mobile hospitals and clinics at the right price point. It is strong, compact and operates on 1 phase 230V power supply. The mobile unit is easy to set up and operate with minimum amounts of maintenance and service required.

It is designed with multiple deployments in mind, meaning it can be used at one site, then dismounted, stored, and re-used at a new location with different climatic requirements. This is an important feature for humanitarian organisations operating with projects across different countries, regions and climate zones. From the deserts of North Africa and the Middle East to the mountains of South America, the jungles of South East Asia and the Arctic areas of Scandinavia this product provides the climatic solution your organisation needs.

View our range of air cooling units and tent coolers suitable for all types of application and commercial purpose on any scale.

Dantherm AC M6 - tent cooler
Dantherm AC M6 - tent cooler
Dantherm AC M6 right
Dantherm AC M6 right
Dantherm AC M6 back
Dantherm AC M6 back
Dantherm AC M6 fresh air intake
Dantherm AC M6 fresh air intake

Key features

  • The AC-M6 is built into a cabinet manufactured from 0.9-2.5mm galvanized and powder coated steel sheet
  • Top finish painting is RAL 9010 or RAL 6031
  • Cooling at outside temperatures up to +51°C
  • Environmentally friendly R454C refrigerant
  • High/low pressure switch ensuring a long compressor lifespan
  • The unit with a heater connects to the mains power supply or to a separate diesel generator via a 10m power cable with a CEE plug
  • The unit without a heater connects to the mains power supply or to a separate diesel generator via a 10m power cable with a Schuko plug
  • Temperature control carried out by a room thermostat
  • Inlet and discharge openings for Ø315mm uninsulated, flexible ducts
  • Easy transportation by either forklift or wheels
  • Setup and operation can be done by a single person
  • Fresh air intake

Product specifications

SpecificationsUnitsAC-M6 with heater
Operating temperature range, cooling
ºC
+20 - +51
Operating temperature range, heating
ºC
-32 - +20
Air flow
m³/h
1,600
Max fresh air via adjustable dampers
m³/h
200
Cooling capacity @ 51/51°C 30% RH
kW
6.5
Cooling capacity @ 51/51°C 30% RH
BTU
22,500
Cooling capacity @ 35/25°C 38% RH
kW
4.2
Cooling capacity @ 35/25°C 38% RH
BTU
14,300
Heating capacity
kW
7.2
Power supply
V/Hz
400/3ph/50
Max. current (heating/cooling)
A
7.4 /11.6
Locked rotor amperage (LRA)
A
35.5
Refrigerant
Type/kg
R454C/1.17
Max. system pressure
bar
28
GWP (Global Warming Potentiel)
-
148
Protection class (electrical panel)
-
IP44
Sound level @1m
dB(A)
63
Fresh air intake
m³/h
0 to 200
Filter (fresh air intake + recirculation)
Type
Coarse
Handling
-
On wheels or by forklift
Power cable with plug
-
10m with CEE16 Amp
Hose connection
Ømm
315
Room thermostat
-
Optional
Safety
CE/UKCA
Product size (h x w x l)
mm
970 x 873 x 798
Weight
kg
108
SpecificationsUnitsAC-M6 w/o heater
Operating temperature range, cooling
ºC
+20 - +51
Operating temperature range, heating
ºC
N/A
Air flow
m³/h
1,600
Max fresh air via adjustable dampers
m³/h
200
Cooling capacity @ 51/51°C 30% RH
kW
6.5
Cooling capacity @ 51/51°C 30% RH
BTU
22,500
Cooling capacity @ 35/25°C 38% RH
kW
4.2
Cooling capacity @ 35/25°C 38% RH
BTU
14,300
Heating capacity
kW
-
Power supply
V/Hz
230/1ph/50
Max. current (heating/cooling)
A
11.6
Locked rotor amperage (LRA)
A
35.5
Refrigerant
Type/kg
R454C/1.17
Max. system pressure
bar
28
GWP (Global Warming Potentiel)
-
148
Protection class (electrical panel)
-
IP44
Sound level @1m
dB(A)
63
Fresh air intake
m³/h
0 to 200
Filter (fresh air intake + recirculation)
Type
Coarse
Handling
-
On wheels or by forklift
Power cable with plug
-
10m with Schuko Amp
Hose connection
Ømm
315
Room thermostat
-
Optional
Safety
CE/UKCA
Product size (h x w x l)
mm
970 x 873 x 798
Weight
kg
106

Product specifications (US)

SpecificationsUnitsAC-M6 with heater
Operating temperature range, cooling
°F
-47
Operating temperature range, heating
°F
-26 to +68
Air flow
SCFM
997
Max fresh air via adjustable dampers
SCFM
124
Cooling capacity @ 124/124°F 30% RH
BTU
21,000
Cooling capacity @ 95/77°F 38% RH
BTU
14,300
Heating capacity
BTU
24,567
Power supply
V/Hz
400/3ph/50
Max. current (heating/cooling)
A
10.6/14.9
Locked rotor amperage (LRA)
A
35.5
Refrigerant
Type/lbs
R454C/1.2
Max. system pressure
bar
28
GWP (Global Warming Potentiel)
-
148
Protection class (electrical panel)
NEMA
3S
Sound level @ 5 feet
dB(A)
65
Fresh air intake
SCFM
0 to 124
Filter (fresh air intake + recirculation)
Type
Coarse
Handling
-
On wheels or by forklift
Power cable with plug
-
33 feet with CEE16 Amp
Hose connection
Øin
12.4
Room thermostat
-
Optional
Safety
CE/UKCA
Product size (h x w x l)
in
38.2 x 34.4 x 31.4
Weight
lbs
238
SpecificationsUnitsAC-M6 w/o heater
Operating temperature range, cooling
°F
+77 to +124
Operating temperature range, heating
°F
N/A
Air flow
SCFM
997
Max fresh air via adjustable dampers
SCFM
124
Cooling capacity @ 124/124°F 30% RH
BTU
21,000
Cooling capacity @ 95/77°F 38% RH
BTU
14,300
Heating capacity
BTU
-
Power supply
V/Hz
230/1ph/50
Max. current (heating/cooling)
A
14.9
Locked rotor amperage (LRA)
A
35.5
Refrigerant
Type/lbs
R454C/1.2
Max. system pressure
bar
28
GWP (Global Warming Potentiel)
-
148
Protection class (electrical panel)
NEMA
3S
Sound level @ 5 feet
dB(A)
65
Fresh air intake
SCFM
0 to 124
Filter (fresh air intake + recirculation)
Type
Coarse
Handling
-
On wheels or by forklift
Power cable with plug
-
33 feet with Schuko Amp
Hose connection
Øin
12.4
Room thermostat
-
Optional
Safety
CE/UKCA
Product size (h x w x l)
in
38.2 x 34.4 x 31.4
Weight
lbs
234

Suitable for

  • Camps and field hospitals
  • Events and festivals
  • Military and aerospace