Dantherm AC-M5 MKII – container cooler
Container coolers
The AC-M5 MKII is designed for window mounting in ISO containers. Together with the trap door system, the air conditioner is mounted in the container wall. It is designed to store within the confinement of the ISO corners during transportation or storage. The AC-M5 MKII is sliding in its trap door system and is deployed from the container for operation. Once deployed, the unit is locked from inside the container when operating.
The unit has no fresh-air intake and is therefore fully CBRN/COLPRO compliant.
AC-M5 MKII can be delivered in either 50Hz or 60Hz versions.
View our range of air cooling units and container coolers suitable for all types of commercial purpose on any scale.
![]()
Dantherm AC-M5 MKII – container cooler
| ![]()
Dantherm AC-M5 MKII trap door
|
![]()
Dantherm AC-M5 installation
| ![]()
Dantherm AC M5 MKII installation
|
![]()
How to mount the Dantherm AC-M5 MKII container cooler
|
Key features
- Manufactured from hot dip galvanized and powder coated steel sheet
- Top finish painting is standard NATO green, RAL 6014
- Air-tight boundary to ambient environment
- Full CBRN/COLPRO compliance (no fresh air intake)
- Delivers cooling in ambient temperatures up to +60°C
- Scroll compressor for high degree of reliability and low noise
- Two-speed selector for the internal fan
- “VENT-only” option for ventilation without cooling
- Stores inside the container during transportation
- Chosen as the NATO standard, conforming to all NATO requirements and norms
- All units have unique NATO stock numbers (NSN)
Product specifications
Specifications | Units | AC-M5 MKII |
---|---|---|
Registered NSN number | - | Yes |
Operating temperature range, cooling | °C | +20 – +60 |
Operating temperature range, heating | °C | -32 – +20 |
Air flow | m³/h | 900 |
Sound level, fan-speed 1 & 2 @ 1m | dB(A) | 49/63 |
Protection class | IP55 | |
Refrigerant | Type/kg | R134a/1.4 |
GWP (Global Warming Potential) | 1300 | |
Nominal cooling capacity | kW/Btu | 4.7/16,000 |
Heating capacity (optional) | kW | 2 |
Power supply | V/Hz | 230/1ph/50 |
Max. running current, cooling/heating | A | 9.8/9.3 |
Locked rotor amperage (LRA) | A | 47 |
Max. power consumption cooling/heating | W | 2,300 |
Hose connection | Ømm | N/A |
Product size (h x l x w) | mm | 482 x 755 x 666 |
Weight | kg | 79 |
Specifications | Units | AC-M5 MKII (60Hz) |
---|---|---|
Registered NSN number | - | Yes |
Operating temperature range, cooling | °C | +20 – +60 |
Operating temperature range, heating | °C | -32 – +20 |
Air flow | m³/h | 970 |
Sound level, fan-speed 1 & 2 @ 1m | dB(A) | 49/63 |
Protection class | IP55 | |
Refrigerant | Type/kg | R134a/1.4 |
GWP (Global Warming Potential) | 1300 | |
Nominal cooling capacity | kW/Btu | 4.7/16,000 |
Heating capacity (optional) | kW | 2 |
Power supply | V/Hz | 208/230/1ph/60 |
Max. running current, cooling/heating | A | 12/9.2 |
Locked rotor amperage (LRA) | A | 56 |
Max. power consumption cooling/heating | W | 2,400 |
Hose connection | Ømm | N/A |
Product size (h x l x w) | mm | 482 x 755 x 666 |
Weight | kg | 74 |
Product specifications (US)
Specifications | Units | AC-M5 MKII (60 Hz) |
---|---|---|
Registered NSN number | Yes | |
Operating temperature range, cooling | °F | +68 to +140 |
Operating temperature range, heating | °F | -26 to +68 |
Air flow | m³/h | 604 |
Sound level, fan-speed 1 & 2 @ 3.3 feet | dB(A) | 49/63 |
Protection class | NEMA | 3S |
Refrigerant | type/lbs | R134a/3.1 |
GWP (Global Warming Potential) | 1,430 | |
Nominal cooling capacity | BTU | 16,000 |
Heating capacity (optional) | BTU | 6,824 |
Power supply | V/Hz | 208/230/1ph/60 |
Max. running current, cooling/heating | A | 9/12/2,002 |
Locked rotor amperage (LRA) | A | 56 |
Max. power consumption cooling/heating | W | 2.4 |
Hose connection | Øin | N/A |
Product size (h x l x w) | in | 19 x 29.7 x 26.2 |
Weight | lbs | 163 |
Suitable for
- Camps and field hospitals