Dantherm AC-M11 – tent cooler
Tent coolers
The AC-M11 air-conditioner is a portable unit developed primarily to provide air-conditioning in temporary or transportable buildings or tents.
The AC-M11 is a small, light-weight aluminium unit built into a rigid steel frame. The unit is designed for outside installation with ducted supply and return air.
View our range of air cooling units and tent coolers suitable for all types of application and commercial purpose on any scale.
![]()
Dantherm AC-M11 – tent cooler
| ![]()
Dantherm AC-M11 white version
|
![]()
Dantherm climate solutions for field camps
| ![]()
Dantherm AC-M11 with ducting
|
![]()
Dantherm AC-M11 tent installation
| ![]()
AC-M air conditioner animation
|
Key features
- Designed for optimal utilization of a standard 20" ISO container
- The AC-M11 is built into a strong metal frame with insulated panels where relevant, powder coated
- Top finish painting is standard sand colour
- Option with built in heating will heat when ambient temperature is below 20°C
- Scroll compressor for a high degree of reliability and low noise level
- Automatic phase surveillance
- Sequential start of units possible
- HP/LP pressostat switches ensuring long compressor lifetime
- Fresh air intake
- Four way fork lift handling
Product specifications
Specifications | Units | AC-M11 |
---|---|---|
Registered NSN number | Yes | |
Operating temperature range, cooling | °C | +20 – +60 |
Operating temperature range, heating | °C | -32 – +20 |
Air flow | m³/h | 1,700 |
Sound level @ 1m | dB(A) | 55 |
Protection class | IPX5 | |
Refrigerant | Type/kg | R134a/2.0 |
Nominal cooling capacity | kW | 11 |
Heating capacity (optional) | kW | 8 |
Power supply | V/Hz | 400/3ph/50 |
Max. running current, cooling/heating | A | 15/16 |
Locked rotor amperage (LRA) | A | 65.5 |
Max. power consumption cooling/heating | W | 4,200/8,800 |
Hose connection | Ømm | 315 |
Product size (h x l x w) | mm | 735 x 1140 x 1140 |
Weight | kg | 162 |
Product specifications (US)
Specifications | Units | AC-M11 |
---|---|---|
Registered NSN number | Yes | |
Operating temperature range, cooling | °F | +68 to +140 |
Operating temperature range, heating | °F | -26 to +68 |
Air flow | SCFM | 1,060 |
Sound level @ 5 feet | dB(A) | 55 |
Protection class | NEMA | 3S |
Refrigerant | Type | R513A |
Nominal cooling capacity | BTU | 37,500 |
Heating capacity (optional) | BTU | 27,300 |
Power supply | V/Hz | 208/3ph/60 |
Max. running current, cooling/heating | A | 30/32 |
Locked rotor amperage (LRA) | A | 65.5 |
Max. power consumption cooling/heating | W | 4,200/8,800 |
Hose connection | Øin | 12.4 |
Product size (h x l x w) | in | 28.3 x 44.9 x 44.9 |
Weight | lbs | 375 |
Suitable for
- Camps and field hospitals
- Events and festivals