Dantherm Group
Dantherm

Calorex Delta series – swimming pool air handling units

Delta 2-4-6-8-10-12-14-16 swimming pool air handling

The sophisticated Delta air handling units incorporate hybrid heat pump and fresh air dehumidification technology. With dynamic heat recovery to swimming pool water and air using a heat pump, a Delta solution is the ultimate choice for a commercial or public indoor swimming pool.

Calorex Delta swimming pool air handling unit
Calorex Delta swimming pool air handling unit
Calorex Delta 16 swimming pool air handling unit
Calorex Delta 16 swimming pool air handling unit
How the Delta system works inside a pool hall
How the Delta system works inside a pool hall
Calorex Delta 4
Calorex Delta 4
Calorex Delta 4 side view
Calorex Delta 4 side view
Calorex Delta 4 back view
Calorex Delta 4 back view
Delta control home screen
Delta control home screen
Delta control panel settings
Delta control panel settings
Calorex Delta set points and switches
Calorex Delta set points and switches
Calorex Delta home screen plus
Calorex Delta home screen plus

Key features

  • Dynamic heat pump heat recovery to pool and air
  • Self-regulating fresh air control with heat recovery
  • Automatic control of exhaust air volume to match pool usage
  • Free-cooling (Delta 1-2)
  • Free-cooling and heat pump air cooling (Delta 4-16)
  • Integral LPHW heat exchangers for pool and air
  • Controllable rpm EC/inverter fans in all models
  • PLC control with 5.7" touchscreen user interface
  • Remote monitoring/control​
  • The minimum security update period for Delta products is zero months

Remote monitoring/control​

  • Screen mirroring to Android/iOS mobile devices using third-party app
  • Screen mirroring to web browser with ActiveX
  • BMS interfaces for Modbus, BACnet IP and BACnet MS/TP
  • Wired remote control interfaces

Options

  • Delta 2-6 single or three phase
  • Delta 8-16 three phase only
  • Upgraded LPHW heat exchanger for air heating
  • Left-hand or right-hand orientation (Delta 4-16)
  • Top, side or bottom supply fan outlet
  • Front or rear supply fan outlet (Delta 14-16)
  • Rear exhaust and fresh air connections (Delta 14-16)
  • Connection for RCU (Delta 16)

Product specifications

SpecificationsUnitsDT 2
Nominal recirculation air flow
m³/h
2,600
Exhaust/fresh air flow (stepped control)
m³/h
130-1,300
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
10.9
Heat to air
Via heat pump (Mode B)
kW
4.9
Via standard LPHW @ 80°C
kW
22
Via upgraded LPHW @ 55°C
kW
19
Total Mode B + standard LPHW
kW
26.9
Heat to pool water
Via heat pump (Mode A)
kW
5.5
Via LPHW @ 80°C
kW
23
Via LPHW @ 55°C
kW
11
Total Mode A + LPHW
kW
28.5
Cooling duty
Total
kW
0
Sensible
kW
0
Nominal power consumed
kW
2.9
R407c gas weight/CO2 equivalent
kg/t
3.0/5.32
Width
mm
1,740
Depth
mm
654
Height
mm
1,685
Weight
kg
310
SpecificationsUnitsDT 4
Nominal recirculation air flow
m³/h
3,000
Exhaust/fresh air flow (stepped control)
m³/h
150-1,500
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
12.5
Heat to air
Via heat pump (Mode B)
kW
5.1
Via standard LPHW @ 80°C
kW
25
Via upgraded LPHW @ 55°C
kW
21
Total Mode B + standard LPHW
kW
30.1
Heat to pool water
Via heat pump (Mode A)
kW
5.8
Via LPHW @ 80°C
kW
33
Via LPHW @ 55°C
kW
16
Total Mode A + LPHW
kW
38.8
Cooling duty
Total
kW
-4.2
Sensible
kW
-2.9
Nominal power consumed
kW
2.9
R407c gas weight/CO2 equivalent
kg/t
6.0/10.64
Width
mm
1,840
Depth
mm
704
Height
mm
1,970
Weight
kg
350
SpecificationsUnitsDT 6
Nominal recirculation air flow
m³/h
4,000
Exhaust/fresh air flow (stepped control)
m³/h
200-2,000
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
16.6
Heat to air
Via heat pump (Mode B)
kW
6.6
Via standard LPHW @ 80°C
kW
30
Via upgraded LPHW @ 55°C
kW
26
Total Mode B + standard LPHW
kW
36.6
Heat to pool water
Via heat pump (Mode A)
kW
8.0
Via LPHW @ 80°C
kW
33
Via LPHW @ 55°C
kW
16
Total Mode A + LPHW
kW
41.0
Cooling duty
Total
kW
-5.5
Sensible
kW
-3.9
Nominal power consumed
kW
3.4
R407c gas weight/CO2 equivalent
kg/t
7.8/13.84
Width
mm
1,840
Depth
mm
704
Height
mm
1,970
Weight
kg
360
SpecificationsUnitsDT 8
Nominal recirculation air flow
m³/h
5,000
Exhaust/fresh air flow (stepped control)
m³/h
250-2,500
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
20.8
Heat to air
Via heat pump (Mode B)
kW
8.0
Via standard LPHW @ 80°C
kW
35
Via upgraded LPHW @ 55°C
kW
30
Total Mode B + standard LPHW
kW
43.0
Heat to pool water
Via heat pump (Mode A)
kW
10.0
Via LPHW @ 80°C
kW
33
Via LPHW @ 55°C
kW
16
Total Mode A + LPHW
kW
43.0
Cooling duty
Total
kW
-6.7
Sensible
kW
-4.7
Nominal power consumed
kW
4.4
R407c gas weight/CO2 equivalent
kg/t
7.8/13.84
Width
mm
1,840
Depth
mm
704
Height
mm
1,970
Weight
kg
370
SpecificationsUnitsDT 10
Nominal recirculation air flow
m³/h
6,000
Exhaust/fresh air flow (stepped control)
m³/h
300-3,000
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
25.0
Heat to air
Via heat pump (Mode B)
kW
10.0
Via standard LPHW @ 80°C
kW
38
Via upgraded LPHW @ 55°C
kW
32
Total Mode B + standard LPHW
kW
48.0
Heat to pool water
Via heat pump (Mode A)
kW
12.5
Via LPHW @ 80°C
kW
40
Via LPHW @ 55°C
kW
20
Total Mode A + LPHW
kW
52.5
Cooling duty
Total
kW
-8.4
Sensible
kW
-5.9
Nominal power consumed
kW
5.9
R407c gas weight/CO2 equivalent
kg/t
9.0/15.97
Width
mm
1,840
Depth
mm
854
Height
mm
1,970
Weight
kg
410
SpecificationsUnitsDT 12
Nominal recirculation air flow
m³/h
7,000
Exhaust/fresh air flow (stepped control)
m³/h
350-3,500
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
29.2
Heat to air
Via heat pump (Mode B)
kW
12.1
Via standard LPHW @ 80°C
kW
42
Via upgraded LPHW @ 55°C
kW
36
Total Mode B + standard LPHW
kW
54.1
Heat to pool water
Via heat pump (Mode A)
kW
15.0
Via LPHW @ 80°C
kW
40
Via LPHW @ 55°C
kW
20
Total Mode A + LPHW
kW
55.0
Cooling duty
Total
kW
-10.1
Sensible
kW
-7.1
Nominal power consumed
kW
7.4
R407c gas weight/CO2 equivalent
kg/t
8.0/14.19
Width
mm
1,840
Depth
mm
854
Height
mm
1,970
Weight
kg
460
SpecificationsUnitsDT 14
Nominal recirculation air flow
m³/h
10,000
Exhaust/fresh air flow (stepped control)
m³/h
670-6,700
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
56.5
Heat to air
Via heat pump (Mode B)
kW
30.0
Via standard LPHW @ 80°C
kW
85
Via upgraded LPHW @ 55°C
kW
72
Total Mode B + standard LPHW
kW
115.0
Heat to pool water
Via heat pump (Mode A)
kW
35.0
Via LPHW @ 80°C
kW
65
Via LPHW @ 55°C
kW
32
Total Mode A + LPHW
kW
100.0
Cooling duty
Total
kW
-23.0
Sensible
kW
-13.0
Nominal power consumed
kW
12.3
R407c gas weight/CO2 equivalent
kg/t
21.5/38.14
Width
mm
2,860
Depth
mm
1,126
Height
mm
2,120
Weight
kg
954
SpecificationsUnitsDT 16
Nominal recirculation air flow
m³/h
12,000
Exhaust/fresh air flow (stepped control)
m³/h
850-8,000
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air
l/h
62.4
Heat to air
Via heat pump (Mode B)
kW
35.0
Via standard LPHW @ 80°C
kW
90
Via upgraded LPHW @ 55°C
kW
77
Total Mode B + standard LPHW
kW
125.0
Heat to pool water
Via heat pump (Mode A)
kW
43.0
Via LPHW @ 80°C
kW
65
Via LPHW @ 55°C
kW
32
Total Mode A + LPHW
kW
108.0
Cooling duty
Total
kW
-28.0
Sensible
kW
-15.0
Nominal power consumed
kW
17.0
R407c gas weight/CO2 equivalent
kg/t
21.5/38.14
Width
mm
2,860
Depth
mm
1,126
Height
mm
2,120
Weight
kg
1,020

Suitable for

  • Leisure and recreation
  • Swimming pools