Dantherm DanX 1-2-3 XD – air handling units
The DanX XD is a very effective ventilation system that uses outdoor air to provide dehumidification using a double heat exchanger that delivers up to a 95% heat recovery. This reduces energy consumption and total operating costs. Making the unit perfect for managing humidity and temperature in the pool room.
![]()
Dantherm DanX XD – swimming pool air handling units
| ![]()
Dantherm DanX 1-2-3 XD – air handling units
|
![]()
Dantherm DanX 1-2-3 XD – air handling units
| ![]()
Dantherm DanX XD diagram
|
Key features
- Built-in user friendly control system for high-quality demand management Automatic monitoring and control of pool hall temperature and humidity The custom-built software runs the unit as efficiently as possible under different conditions
- Double crossflow heat exchangers with a high efficiency of more than 95% and a low pressure drop
- Built-in by-pass for free cooling in summertime
- Highly energy-efficient EC plug fans
- Efficient M5/ePM10 70% and F7/ePM1 55% compact filters with low pressure drop
- Self-bearing cabinet with hot-dip galvanised, powderpainted sandwich panels with 50mm mineral wool insulation, internal partition walls with 30mm and bottom frame with adjustable feet
- Designed to withstand the aggressive swimming pool environment (Corrosion class C4 according to EN/ISO 12944-2), with epoxy-coated crossflow heat exchangers heating coil with aluminium frame, prepainted fins and epoxy coating to protect all fasteners, bolts, nuts
- Two large inspection doors with strong hinges and tongue locks and handles for easy access for service
- All-in-one box solutions for easy and quick installation – all sensors and electrical components pre-connected
- BMS communication with either Modbus or BACnet
DanX XD with double cross flow heat exchanger
The DanX XD is a very effective ventilation system that uses outdoor air to provide dehumidification using a double heat exchanger that delivers up to a 95% heat recovery. This reduces energy consumption and total operating costs. Making the unit perfect for managing humidity and temperature in the pool room.
The built-in mixing function takes care not to add any more outdoor air than necessary to provide a comfortable indoor climate. Free cooling is also an option during summer, when the unit can add up to 100% outdoor air into the pool area through a by-pass.
The unit's compact, integrated design enables optimal installation in the technical room. Convenient top or side connections ensure easy access to ducts.
Product specifications
Specifications | Units | DANX 1 XD |
---|---|---|
Nominal air volume | m³/h | 1,000 |
Max. air volume | m³/h | 1,300 |
Max. external duct pressure | Pa | 350 (at nominal air volume) |
Outdoor air volume | % | 0-100 |
Dehumidification capacity VDI 2089 | kg/h | 7 (at 30°C/54% indoor) |
Max. total power consumption | kW | 1.1 |
Power supply | V/Hz | 230/1ph/50 |
Product size (w x d x h) | mm | 1750 x 515 x 1570 |
Weight | kg | 254 |
Specifications | Units | DANX 2 XD |
---|---|---|
Nominal air volume | m³/h | 1,750 |
Max. air volume | m³/h | 2,100 |
Max. external duct pressure | Pa | 350 (at nominal air volume) |
Outdoor air volume | % | 0-100 |
Dehumidification capacity VDI 2089 | kg/h | 11 (at 30°C/54% indoor) |
Max. total power consumption | kW | 1.2 |
Power supply | V/Hz | 230/1ph/50 |
Product size (w x d x h) | mm | 1750 x 780 x 1570 |
Weight | kg | 344 |
Specifications | Units | DANX 3 XD |
---|---|---|
Nominal air volume | m³/h | 2,750 |
Max. air volume | m³/h | 3,700 |
Max. external duct pressure | Pa | 350 (at nominal air volume) |
Outdoor air volume | % | 0-100 |
Dehumidification capacity VDI 2089 | kg/h | 18 (at 30°C/54% indoor) |
Max. total power consumption | kW | 1.9 |
Power supply | V/Hz | 230/1ph/50 |
Product size (w x d x h) | mm | 2250 x 890 x 1990 |
Weight | kg | 465 |
Suitable for:
- Leisure and recreation
- Swimming pools